FCU actuator replacement planning
HVAC Engineer · Certified HVAC Specialist · Manager at DENAIR, Dubai
Start with the reason for replacement
A quotation for a “24V actuator” or “230V actuator” leaves important questions unanswered. Before approving a replacement on a chilled-water fan-coil unit (FCU), ask which fault was found, which exact part is proposed and how it matches the existing valve and controls.
This checklist concerns water-valve actuators. If the starting complaint is continued cooling after switch-off, first use our guide to an FCU that keeps cooling with the thermostat Off. The symptom alone does not establish that the actuator needs replacement.
Describe a missing, detached or disconnected actuator
In a valve-controlled chilled-water FCU, the actuator operates the water-control valve in response to the controls. The fan circulates air across the coil. A running fan therefore does not show that the valve actuator is present or working.
Ask the technician to identify the valve assembly and use a clear description in the report:
Missing: the assembly needs an actuator, but none is fitted or found. Confirm the intended valve arrangement before ordering a part from a photograph.
Detached: the actuator is present but not mounted on the valve. Its cable may still be connected. Being off the valve does not make it safe to handle.
Electrically disconnected: the technician has found a disconnected cable or connector. Keep this separate from a test finding of no power or no control command, which needs its own investigation.
Incorrectly fitted: the part is present, but its mounting or valve match needs correction. Ask which requirement is not met rather than judging compatibility by appearance.
Have the report pair the observed condition with the affected unit, component identification and the check still needed. A detached actuator or a loose cable alone does not establish the valve position, the reason for the fault or the need to replace the part. Leave ceiling access, connection checks and handling to the technician.
Was the actuator removed during renovation?
The work record should establish why it was removed. Ask whether this was part of valve or controls work, a temporary service step or an alteration that still needs finishing. Do not infer the reason or who removed it from a photograph. If the history is unavailable, have that uncertainty recorded.
Before the ceiling closes, ask the contractor to identify where the removed part is, whether it will be refitted or replaced, who will complete the work and what the unit's operating status is in the meantime. Keep reinstatement and its tests on the outstanding-work list.
For example, Siemens' SSA instructions address disconnection during servicing and require the valve to be correctly mounted for commissioning. The installed model needs its own procedure. Refitting a component should be followed by the relevant control and valve checks described below.
Record the exact model, supply and control signal
Ask the technician to record the actuator's complete model code, valve-body identification and controller model. Include any previous alterations. An earlier replacement may itself be incompatible, so copying its voltage label is not enough.
The specification should distinguish supply voltage from the command that positions the actuator. For example, Siemens' SSA actuator data sheet lists SSA81 variants with 24V AC supply and three-position control, while SSA61 variants use 24V AC/DC supply and a 0–10V DC control signal. SSA31 variants use 230V AC supply and three-position control.
These are model-specific examples, not interchangeable choices. Ask for written confirmation that the proposed actuator matches the installed controller's output and the available supply, including whether AC or DC is required.

Still from an original DENAIR service video showing a detached actuator during an inspection.
Match the actuator to the valve body
The replacement proposal should identify the manufacturer's approved valve-and-actuator combination, including any specified mounting accessory. Ask the technician to confirm:
The mounting connection, dimensions and permitted orientation.
The required linear travel or rotary movement.
The force or torque needed to operate the valve.
Any flow-setting or calibration requirements.
For comparison, the Belimo CQ24A-SR is a rotary zone-valve actuator with 1 Nm torque and snap mounting. Those details describe that product, not a universal FCU replacement specification. A part that fits in the ceiling still needs a verified mechanical match to the valve.
Confirm normal and power-loss positions
Ask what the complete valve assembly should do during normal commands and if power is lost. Confirm whether the design requires a fail-safe return position or allows the actuator to remain where it is.
Danfoss' TWA range includes normally closed and normally open versions, referring to valve positions without actuator power. By contrast, Siemens documents SSA61 actuators as maintaining their position when supply power is removed. Do not assume every actuator closes the valve on power loss, or that a replacement with the same voltage preserves the intended behaviour.
Include access and installation condition in the quote
Ask whether the actuator can be removed and refitted through the existing opening, and whether the valve body can remain in place. If valve work is also proposed, have the contractor identify building permissions, water-system isolation and any ceiling reinstatement separately. Our FCU access-hatch guide explains why filter access may not reach the valve.
Have the technician inspect moisture exposure, mounting orientation and nearby insulation against the selected product's requirements. For example, Belimo specifies non-condensing humidity for the CQ24A-SR. Replacing a component without addressing an unsuitable installation can leave the cause of damage unresolved.
Electrical identification, isolation, testing and replacement belong with qualified technicians. Do not open electrical covers, apply power to test an actuator or alter its supply yourself.
Agree the evidence you will receive after fitting
Before authorising work, ask for a handover record covering the fitted model and valve, any required calibration, the commands tested and the resulting valve response. Include the relevant water-side operating conditions and any check that could not be completed. An indicator moving is only one part of demonstrating successful operation.
Keep the original fault finding alongside the completed tests and outstanding actions. To discuss a replacement proposal, send DENAIR's AC repair and diagnostics team the service report, quotation and equipment details you already have. Leave concealed labels and components for the technician to inspect.